Печать


DOI: https://doi.org/10.15407/techned2017.01.071

EVALUATION OF HIGH-VOLTAGE CIRCUIT BREAKER INTERRUPTION RESOURCE

Journal Tekhnichna elektrodynamika
Publisher Institute of Electrodynamics National Academy of Science of Ukraine
ISSN 1607-7970 (print), 2218-1903 (online)
Issue No 1, 2017 (January/February)
Pages 71 – 80

 

Authors
B.S. Stognii1, M.F. Sopel1, L.D. Tretiakova2, E.M. Tankevych1, A.V. Panov1, V.I. Pankiv1
1 – Institute of Electrodynamics of the National Academy of Sciences of Ukraine,
Peremohy pr., 56, Kyiv, 03057, Ukraine,
e-mail: Этот e-mail адрес защищен от спам-ботов, для его просмотра у Вас должен быть включен Javascript
2 – National Technical University of Ukraine “Kyiv Polytechnic Institute”,
pr. Peremohy, 37, Kyiv, 03056, Ukraine

 

Abstract

The overall effect of precision of interruption curve approximation, accuracy of current measurement and evaluation of root-mean-square value of circuit breaker interrupted current on precision its switching resource under condition was investigated. Based on the results of several ways of approximation of interruption curve of circuit breaker, using different amount of points, given by manufacturer, the conditions of qualitative and accurate approximation of such curve were identified. ABB HPL 362 B1 circuit breaker was considered as example and it was shown that one of the possible ways to increase the accuracy and improve technology of circuit breaker interruption resource evaluation is its resource curve approximation by using cubic spline and improving the accuracy of measurement of instantaneous values of fault currents in the period of interruption of fault currents. References 11, figures 6, tables 3.

 

Key words: high-voltage circuit breaker, interruption resource, approximation, interrupted current, current transformer.

 

Received:    15.09.2016
Accepted:    09.12.2016
Published:  19.01.2017

 

References

1. Grabko V.V. Methods and means of technical diagnostics of circuit breakers of large electric currents: thesis doctor of Philosophy: 05.11.16.  Vinnitsa, 1990.  174 p. (Rus)
2. Minkin I.S., Romanov A.A. Algorithm assessment of residual resource of circuit breakers. Elektricheskie stantsii.  2004.  No 12.  Pp. 58-62. (Rus)
3. Rogoza V.V., Sopel M.F., Cherniakin V.P., Lesnovska S.L. The algorithm for calculation of residual life of circuit breakers. Avtomatizatsiia i releinaia zashchita v energosistemakh. Sbornik nauchnykh trudov.  1992.  Pp. 167-170. (Rus)
4. Stognii B.S., Sopel M.F., Pankiv V.I., Tankevich E.M. Current transformer mathematical model based on the Jiles-Atherton theory of ferromagnetic hysteresis. Tekhnichna Elektrodynamika.  2016.  No 3.  Pp. 1-8. (Ukr)
5. Stognii B.S., Sopel M.F., Maksymchuk V.F., Tutyk V.L., Mychaylevski O.S., Panov A.V., Stasiuk O.I., Tarasevych P.Y., Voitov D.V. Microprocessor system for monitoring and prediction of interruption resource of SF6 high-voltage circuit breaker. Pat. 73398 Ukraine, MPK G 07 C 3/10. 2012. (Ukr)
6. GOST 4.176-85. System of product-quality indices. High-voltage electrical apparatus. Nomenclature of indices.  Moskva: Izdatelstvo Standartov, 1986.  17 p. (Rus)
7. De Grijp M.H.B., Bedet J.S., Hopkins R.A. Greyling Condition monitoring of high voltage circuit breakers. IEEE 4th AFRICON Conference in Africa, University of Stellenbosch (South Africa).  September 25-27, 1996.  Pp. 880-885.
8. Fan Y., Chenxi Q., Xiaohui Z., Jun D., Xiaoguang H. Integrated state test system of high voltage circuit breackers based on embedded technology. 2011 6th IEEE Conference on industrial electronics and applications (ICI-EA), Beijing (China).  June 21-23, 2011.  Pp. 1605-1609.
9. Jeyaraj S.G., Habtay Y.  Effective and efficient circuit breaker analysis. IET Conference on reliability of transmission and distribution networks (RTDN 2011), London (United Kingdom). November 22-24, 2011.  Pp. 157-162. DOI:  https://doi.org/10.1049/cp.2011.0532

10. Jin X., Liujun Z., Xiaoquang H., Liang L., Lei Z. Development of on-line monitoring system for SF6 circuit breaker. 2011 6th IEEE Conference on industrial electronics and applications (ICIEA), Beijing (China).  June 21-23, 2011.  Pp. 537-541.
11. Kim M.-H., Kim K.-H., Smajkic A., Kapetanovic M., Muratovic M. Influence of contact erosion on the state of SF6 gas in interrupted chambers of HV SF6 circuit breakers. 2014 IEEE International power modulator and high voltage conference (IPMHVC), Santa Fe (New Mexico, USA).  June 1-5, 2014.  Pp. 466-469.

 

PDF