PDF Печать E-mail

DOI: https://doi.org/10.15407/techned2019.03.060

ELECTROMAGNETIC VIBRATION DISTURBING FORCES OF POWERFULL TWO- AND FOUR-POLE TURBOGENERATORS OF NUCLEAR POWER PLANTS OF UKRAINE

Journal Tekhnichna elektrodynamika
Publisher Institute of Electrodynamics National Academy of Science of Ukraine
ISSN 1607-7970 (print), 2218-1903 (online)
Issue No 3, 2019 (May/June)
Pages 60 – 66

 

Authors
Yu.M. Vaskovskyi1*, A.M. Melnyk2**
1- National Technical University of Ukraine Igor Sikorsky Kyiv Polytechnic Institute,
pr. Peremohy, 37, Kiyv, 03056, Ukraina,
e-mail: Этот e-mail адрес защищен от спам-ботов, для его просмотра у Вас должен быть включен Javascript
2- Institute of Electrodynamics of the National Academy of Sciences of Ukraine,
pr. Peremohy, 56, Kyiv, 03057, Ukraine,
e-mail: Этот e-mail адрес защищен от спам-ботов, для его просмотра у Вас должен быть включен Javascript
* ORCID ID : http://orcid.org/0000-0003-1262-0939
** ORCID ID : http://orcid.org/0000-0002-7492-3110

Abstract

A comparative analysis of the electromagnetic vibration disturbing forces occurring in the stator of two- and four-pole powerful turbogenerators operating on nuclear power plants of Ukraine on the basis mathematical model of the electromagnetic field was consider. The spectral analysis of of the electromagnetic vibrational forces was carry out. A spectrum of the electromagnetic vibrational forces has significant harmonics of frequencies 200, 300, 400 Hz, which are multiples of 100 Hz of the main vibrational force was show. Experimental investigation of the eigenfrequency modes of the end of stator winding was carry out. There is a danger of response eigenfrequency modes at the specified multiple frequencies. Moreover, due to the design structure of two-pole turbogenerators are more dangerous. References 5, figures 8, tables 2.

 

Key words: turbogenerator, electromagnetic vibration disturbing forces, implicit-pole rotor, eigenfrequency, spectral analysis, response.

 

Received:    30.10.2018
Accepted:    07.12.2018
Published:  05.03.2019

 

References

1. Abramov A.I., Izvekov V.I., Serihin N.A. Designing of turbogenerators. Moskva: Vysshaia shkola, 1990. 336 p. (Rus)
2. Vaskovskyi Yu.M., Melnyk A.M. The electromagnetic vibration disturbing forces in turbogenerator with a glance of current asymmetry of stator winding. Tekhnichna Elektrodynamika. 2017. No 1. Pp. 52-57. (Ukr)
3. Vaskovskyi Yu.M., Shumilov Yu.A., Shtogrin A.V. Analysis of vibration-exciting axial forces in a powerful turbogenerator stator core. Electrikal engineering & Electromechanics. 2009. No 2. Pp. 21-26. (Rus)
4. Milykh V.I., Pototskyi D.V. The numerical-field analysis of power and energy processes in the turbo-generator at load unbalance. Tekhnichna Elektrodynamika. 2017. No 4. Pp. 29-35. (Rus)
5. URL: http://atominfo.bg/wp-content/uploads/2012/01/GigaTop.pdf (Accessed 11.06.2018).

PDF